Special extract

Rooms with special needs get their own extract that follows a trigger. Each state – low or high – has its own fan command and actions for supply and extract dampers.

  • Trigger from a room switch, binary signal, humidity with setpoint and hysteresis, or AHU operation
  • Fan controlled by 0–10 V or percent per state
  • Supply and extract dampers set to closed, Vmin, Vmax or auto
  • Interlock with the air handling unit and supervision of run feedback, fan fault and airflow deviation
sd.econex.no/building-a/ventilation
Illustration
Ventilation
Building A · 3 air handling units
Running
Air handling units
UnitStatusSupplyExtractImbalance
360.001Office wingAuto8,420 m³/h8,173 m³/h2.9 %
360.002Canteen/meetingAuto3,155 m³/h2,928 m³/h7.2 %
360.003Garage/storageAuto1,885 m³/h1,857 m³/h1.5 %
360.001 · Air handling unitSFP 1.74121 Pa
VAV dampers · 360.001
2.01 Office east
46%
2.02 Office west
52%
2.03 Meeting room
61%
2.04 Canteen
38%
2.05 Office north
49%
2.06 Storage
22%
2.07 Changing room
31%
2.08 Reception
43%
Special extract
SA-01
Kitchen spot extract
1,243m³/hRunning
SA-02
Waste room
426m³/hRunning
SA-03
Lab spot extract
0m³/hStandby
SA-04
Garage CO
964m³/hDemand